Standard units are available with operating voltages
from 5KV to 190KV AC PK or DC, with peak test voltage to 300KV PK,
continuous currents to 1,200 amps and interrupt currents to 28,000 amps.
Capacitor discharge closing currents up to 100,000 amps are possible
depending on time constant of discharge down to 37% level.
With repeated high speed DC interruptions or crobar
type operations in DC circuits, both transformers and loads must be
protected from possible transient overvoltages and inrush currents.
Transformers must be well braced and end turns especially well insulated.
Loads, especially inductive loads, must have capacitance and/or non-linear
resistance in parallel at their terminals and on the output terminals of
the transformer. Capacitors with at least 1.5 times voltage rating (in the
order of .01 to 0.25 mfd) in series with 1 to 2 ohms per KV, are
recommended. GE Thyrite or similar nonlinear resistance carefully rated
for appropriate operating current is also helpful. To limit inrush on
re-energizing after a crobar has tripped a primary breaker, a dual
step-start contactor or circuit breaker is recommended. See
Three Pole HV Vacuum Contactors / Circuit
Breakers for further power
control information.
Two auxiliary SPDT contacts are standard on each model.
Additional auxiliary contacts can be ordered.