DIGITAL AC HIPOT
0-50kV RMS
0-60kV RMS
0-100kV RMS
| |
 |
Special Digital Control
Model ACC401- -D
HV Vacuum Device Tester with
X-Ray Monitor and Emission and
Breakdown Indicator.
115V or 230V Digital Variable Control Unit. |
|
|
Specifically designed for
Calibrating High Voltage Measurement Devices
or Testing High Voltage Equipment, Insulation and optionally
HV Vacuum Interrupters or other HV Vacuum Devices. |
Model ACC-401-50-D, ED
0-50kV RMS Portable
Model ACC-401-60-D, ED
0-60kV RMS Mobile
Model ACC-401-100-D, ED
0-100kV RMS Mobile
Ross Engineering’s Hipot Control Unit features Variable Voltage Control
with safety return to zero. It provides adjustable current overload
trip, a 4½ digit digital voltmeter for easy viewing and a AC digital
milliammeter. Its simplified design is excellent for testing and
accurately calibrating high voltage instrumentation or measuring AC
insulation leakage current, and testing breakdown or withstand voltage
for any type of device where AC Hipot testing is appropriate within its
current limit.
Total 50kV system weight is 76 lbs for epoxy potted transformer
portability. Total 60kV and 100kV system weight is approximately 170 lbs
to 850 lbs. Shipping crate adds approximately 100 lbs. The larger Hipot
Transformers are oil filled. Total shipping weight is approximately 300
lbs to 950 lbs.
The secondary of the transformer is provided with a control winding or
voltage divider which permits monitoring of high voltage output up to
50kV, 60kV or 100kV even to 130kV RMS short time depending on model.
The basic HV Transformer rating is 5 to 25mA continuous, higher short
time. Maximum continuous Hipot output current is limited by the control
unit with current limiting resistors and adjustible overload sensing. A
special control unit is required if higher AC output current is desired
for high capacitance loads and for HV Vacuum Interrupters or other HV
Vacuum devices.
1. Input Voltage: 120V or optional 230V AC, 50/60Hz.
2. Output Voltage: 0-50kV, 0-60kV, 0-100kV RMS up to 130kV RMS short
time with built in 4½ digit voltmeter.
3. Rated current: 5 to 25mA continuous (up to 4 times short time), with
built-in 3½ or 4½ digit AC milliammeter.
4. Adjustable current overload trip.
5. Voltage stability: ±0.5% Depending on input voltage and current.
Voltage regulator optional.
6. Voltage accuracy: ±0.5%, ±0.2% with included optional certified
correction chart.
7. Current stability: ±1.0%.
8. Current accuracy: ±1.0%.
9. Environment: operation: 0ºC to +50ºC. Storage: -10º to +75ºC.
10. Temperature Coefficient: 0.2% / °C.
11. 0-1 minute timer optional.
12. NIST traceable calibration report.
13. Model ACC401 can also have optional X-Radiation Monitor and HV
Vacuum Device Emission and Breakdown Indicator.
14. Analog Voltmeter, Analog Milliammeter and separate HV Transformers
are also available.

Portable HV Transformer 50kV RMS
to over 10mA continuous |

Mobile HV Transformer 60kV, 100kV RMS
5mA to over 25mA continuous |
|